DMP-100

Point heat and smoke multi-sensor detector

The point multi-sensor detector combines in a single device the functionality of visible smoke detection, the rate-of-rise detection and the detection of cases of exceeding the limit temperature. Owing to this combination of detection technologies, the DMP-100 detector can detect many different sources of fire.

  • unique Swirl chamber accelerates smoke detection
  • test fires detected: TF-1 to TF-5 acc. to EN54-7 and TF-1, TF-6 and TF-8 acc. to ISO/TS 7240-9:2006
  • A1R heat detector in conformance with EN54-5
  • stainless-steel precision filter
  • failure signalling – contamination of measuring chamber
  • simple detector installation at the base of DB-100
  • possibility of connecting an external status indicator
DMP-100
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.

Documentation

general information manual
updated: 2022-12-05
363 KB

Certificates

Other certificates
updated: 2022-11-22
2.92 MB
Declaration of performance
updated: 2022-11-22
846 KB
EU declaration of conformity
updated: 2023-01-02
855 KB

Technical Data

Enclosure dimensions
ø108 x 49 mm
Operating temperature range
-25...+50 °C
Supply voltage
10,5...26 V DC
Weight
94 g
Maximum humidity
93±3%
Class according to EN 54-5 (heat sensor)
A1R
Minimum static response temperature
54 °C
Maximum static response temperature
65 °C
Current draw when detecting
40 µA
Current draw when emitting an alarm
23 mA

Information materials

3leaflet - installer

5product data sheet